Protection Relays

 

Protection and diagnostic relay type DIA-IGTV

The main application of the relay is in power supply systems for traction lines and the device performs various protection functions including “remote” failure functions. It also provides information on the status of the circuit breaker for preventive maintenance planning.

DIA-IGTV has the following functions incorporated in one single module:

- Circuir Breaker diagnostic DIA-I : this module provides information on the general status of the circuit breaker and contact and arc-chute wear.

- Load current analyzer DIA-G: this device analyses current rate of rise and detects for line faults rather than multiple motors start near the substation.

- Thermal image DIA-T: this modules monitors the temperature trend of a component (rectifier, cable, motor, contact line, etc..)

Technical characteristics

Applicable standard:
CEI 41-1
Rated insulation voltage: 600V
Test voltage at industrial frequency: 2 kV – 50 Hz – 1 min
Lighting test voltage: 5 kV ­ 1,2/50 µs
Precision of reference values of interaction quantities: ± 2÷3% or measurement;
± 3÷5% for time
High frequency trouble insensitiveness: 2,5 and 1 kV – 1 MHz
Standard auxiliary supply voltages: 24 – 220 Vdc or Vac
Input:
Rated current : 20mA
Overload capacity: 60mA x 1 sec, 35 mA permanent
Impedance: 150 Ω - 5V
Output relay
Occasional overload:
Ith: 5A
Vn: 380 Vac – 125 Vdc
Breaking capacity:
1250 VA – 250 Vac / 1A – 380 Vac
150w –30 Vdc / 0,2 A – 125Vdc with L/R = 7 ms

Line test device type DIA-LP

The purpose of the line test circuit is to verify the condition of the main line preventing the DC circuit breaker closing in case of overload or short circuit condition.

The line testing device for voltage 750 V is DIA LP/LM type.

The line testing device for voltages 1500/3000 V is DIA LP31 type.

The line testing system consist of these main parts:

- Current injection circuit, connected in parallel with the DC circuit breaker, consisting of a fuse protected contactor with integrity indication and a suitable power resistance.

- Logic device which controls the operation of the injection circuit and is connected with other control devices and/or equipments.

Technical characteristics DIA-LP

Rated insulation voltage: 600V
Insulation Test voltage: 2 kV – 50 Hz – 1 min
Rated auxiliary voltage :110 Vdc
Output relay : Tth= 5A – Vn=380 Vac – Vn=125 Vdc
Precision of reference values of interaction quantities:
± 2÷ 3% for measurement;
± 3÷ 5% for time
High frequency trouble insensitiveness: 2,5 and 1 kV – 1 MHz
Input:
Rated current : 20mA
Overload capacity: 60mA x 1 sec, 35 mA permanent
Impedance : 150 Ω - 5V

Technical characteristics DIA-LM

Rated voltage of main circuit: 750 V
Insulation Test voltage: 4 kV – 50 Hz – 1 min
Rated auxiliary voltage :110 Vdc