IRA

High Speed Circuit Breaker type IRA with Holding Coil

The IRA series are single pole, magnetic blow-out, trip free, air circuit breakers. The breakers is electromagnetic type. The breakers is held closed by holding coil and is equipped with a direct acting over – current trip device unidirectional.

 

 

Technical Characteristics      
Rated voltage [V] Un 1500 3000
Overvoltage category   OV3 OV3
Degree of pollution   PD3 PD3
Rated current [A] In Up to 3000 Up to 3000
       
Short circuit breaking capacity Ue 1800 [V] 3600 [V]
  Îcc 100 [kA]- Peak 60 [kA]- Peak
  Icc 60 [kA]- Steady State 40 [kA]- Steady State
       
Tripping direction   Unidirectional Unidirectional
Mechanical life (EN 50123) N 20.000 20.000
       
Dielectric withstand voltage [50Hz, 60s]      
Across open main contacts UA 4.5 kV 7.5 kV
Between main contacts and earth UA 5.4 kV 15 kV
Between auxiliary and earth UA 3 kV 3 kV
       
Auxiliary circuit      
Rated voltage [Vdc] Un 24 ÷ 250 24 ÷ 250
Type of holding device [EM: Electtromagnetic]   EM EM
       
Auxiliary contacts      
Available contacts   4 NO+ 4 NC 4 NO+ 4 NC
Max breaking capacity on Ohmic load [A] In 4 4
       
Ambient conditions      
Temperature Tamb -5 + 40° C 5 + 40° C
Altitude h < 1400 m < 1400 m
       
Installation      
Mounting position   Vertical Vertical
Fixing   Bolted on the base Bolted on the base
Connection of main circuit   Cables or busbars Cables or busbars
Weight (1500 A version) kg 178 225
Dimensions (1500 A version) mm 801x302x1133h 801x302x1070h
Execution [F= Fixed; W= Withdrawable]   F F