IR6000

High Speed Circuit Breaker type IR6000 with Electromagnetic Latch

The IR6000 Electromagnetic latch series are fixed or withdrawable, single pole magnetic blow-out, trip free, air circuit breakers.

The closing mechamism is an independent motor operated type.

The breaker is held closed by holding coil and is equipped with a direct acting over – current trip device which may be either unidirectional or bidirectional.

The Breaker confroms to ANSI C 37-14, ANSI C 37-16 and EN 50123 Standard.

 

 

Technical Characteristics          
Rated voltage [V] Un 750 1200 1500 3000
Overvoltage category   OV3 OV3 OV3 OV3
Degree of pollution   PD3 PD3 PD3 PD3
Rated current [A] In Up to 8000 Up to 8000 Up to 8000 Up to 4000
           
Short circuit
breaking capacity

(ANSI C 37-14)
(IR6000 4kA)
Ue 800 [V] 1200 [V]    
  Icc 200 [kA] -
Peak
132 [kA] -
Peak
   
  Icc 120 [kA] -
Steady State
80 [kA] -
Steady State
   
           
Short circuit
breaking capacity

(EN50123)
Un 800 [V]   1800 [V] 36800 [V]
  Icc 120 [kA] -
Peak
  100 [kA] -
Peak
61 [kA] -
Peak
  Icc 90 [kA] -
Steady State
  70 [kA] -
Steady State
40 [kA] -
Steady State
          100 [kA] -
Peak
          70 [kA] -
Steady State
           
Tripping direction   Uni and
Bidirectional
Uni and
Bidirectional
Uni and
Bidirectional
Uni and
Bidirectional
Trip setting
of overcurrent release
I From 500
to 20000 [A]
From 500
to 20000 [A]
From 500
to 20000 [A]
From 500
to 20000 [A]
Mechanical life
(EN 50123)
N 20.000 20.000 20.000 20.000
           
Dielectric withstand
voltage
[50Hz, 60s]
         
Across open main contacts UA 6 kV 6 kV 10 kV 15 kV
Between main contacts
and earth
UA 6 kV 6 kV 10 kV 15 kV
Between auxiliary
and earth
UA 2,5 KV 2,5 KV 2,5 KV 2,5 KV
           
Auxiliary circuit          
Rated voltage [Vdc] Un 24 ÷220 24 ÷220 24 ÷220 24 ÷220
Type of closing device   With servomotor With servomotor With servomotor With servomotor
Type of holding device
[EM: Electtromagnetic]
  EM EM EM EM
           
Auxiliary contacts          
Available contacts   6 NO + 6 NC 6 NO + 6 NC 6 NO + 6 NC 6 NO + 6 NC
Max breaking capacity
on Ohmic load [A]
In 3 3 3 3
Thermal current [A] Ith 5 5 5 5
           
Ambient conditions          
Temperature Tamb -5 + 40° C -5 + 40° C -5 + 40° C -5 + 40° C
Altitude h < 1400 m < 1400 m < 1400 m < 1400 m
           
Installation          
Mounting position   Vertical Vertical Vertical Vertical
Fixing   Bolted
on the base
or mounted
on truck
Bolted
on the base
or mounted
on truck
Bolted
on the base
or mounted
on truck
Bolted
on the base
or mounted
on truck
Connection of main circuit   Cables
or busbars
Cables
or busbars
Cables
or busbars
Cables
or busbars
           
Weight –
Up to 4kA
kg 160 160 165 202
Dimensions –
Up to 4kA
mm 768 x 307 x 1030h 768 x 307 x 1030h 768 x 307 x 1030h 788 x 307 x 1083h
           
Weight –
Up to 8kA
kg 162 162 167  
Dimensions –
Up to 8kA
mm 790 x 360 x 1030h 790 x 360 x 1030h 790 x 360 x 1030h  
           
Execution
[F= Fixed; W= Withdrawable]
  F/W F/W F/W F/W