High Speed Circuit Breaker type IR6000 with Electromagnetic Latch
The IR6000 Electromagnetic latch series are fixed or withdrawable, single pole magnetic blow-out, trip free, air circuit breakers.
The closing mechamism is an independent motor operated type.
The breaker is held closed by holding coil and is equipped with a direct acting over – current trip device which may be either unidirectional or bidirectional.
The Breaker confroms to ANSI C 37-14, ANSI C 37-16 and EN 50123 Standard.
| Technical Characteristics | |||||
| Rated voltage [V] | Un | 750 | 1200 | 1500 | 3000 |
| Overvoltage category | OV3 | OV3 | OV3 | OV3 | |
| Degree of pollution | PD3 | PD3 | PD3 | PD3 | |
| Rated current [A] | In | Up to 8000 | Up to 8000 | Up to 8000 | Up to 4000 |
|
Short circuit breaking capacity (ANSI C 37-14) (IR6000 4kA) |
Ue | 800 [V] | 1200 [V] | ||
| Icc | 200 [kA] - Peak | 132 [kA] - Peak | |||
| Icc | 120 [kA] - Steady State | 80 [kA] - Steady State | |||
|
Short circuit breaking capacity (EN50123) |
Un | 800 [V] | 1800 [V] | 36800 [V] | |
| Icc | 120 [kA] - Peak | 100 [kA] - Peak | 61 [kA] - Peak | ||
| Icc | 90 [kA] - Steady State | 70 [kA] - Steady State | 40 [kA] - Steady State | ||
| 100 [kA] - Peak | |||||
| 70 [kA] - Steady State | |||||
| Tripping direction | Uni and Bidirectional | Uni and Bidirectional | Uni and Bidirectional | Uni and Bidirectional | |
|
Trip setting of overcurrent release |
I |
From 500 to 20000 [A] |
From 500 to 20000 [A] |
From 500 to 20000 [A] |
From 500 to 20000 [A] |
|
Mechanical life (EN 50123) |
N | 20.000 | 20.000 | 20.000 | 20.000 |
| Dielectric withstand voltage [50Hz, 60s] | |||||
| Across open main contacts | UA | 6 kV | 6 kV | 10 kV | 15 kV |
| Between main contacts and earth | UA | 6 kV | 6 kV | 10 kV | 15 kV |
| Between auxiliary and earth | UA | 2,5 KV | 2,5 KV | 2,5 KV | 2,5 KV |
| Auxiliary circuit | |||||
| Rated voltage [Vdc] | Un | 24 ÷220 | 24 ÷220 | 24 ÷220 | 24 ÷220 |
| Type of closing device | With servomotor | With servomotor | With servomotor | With servomotor | |
| Type of holding device [EM: Electtromagnetic] | EM | EM | EM | EM | |
| Auxiliary contacts | |||||
| Available contacts | 6 NO + 6 NC | 6 NO + 6 NC | 6 NO + 6 NC | 6 NO + 6 NC | |
| Max breaking capacity on Ohmic load [A] | In | 3 | 3 | 3 | 3 |
| Thermal current [A] | Ith | 5 | 5 | 5 | 5 |
| Ambient conditions | |||||
| Temperature | Tamb | -5 + 40° C | -5 + 40° C | -5 + 40° C | -5 + 40° C |
| Altitude | h | < 1400 m | < 1400 m | < 1400 m | < 1400 m |
| Installation | |||||
| Mounting position | Vertical | Vertical | Vertical | Vertical | |
| Fixing | Bolted on the base or mounted on truck | Bolted on the base or mounted on truck | Bolted on the base or mounted on truck | Bolted on the base or mounted on truck | |
| Connection of main circuit | Cables or busbars | Cables or busbars | Cables or busbars | Cables or busbars | |
| Weight – Up to 4kA | kg | 160 | 160 | 165 | 202 |
| Dimensions – Up to 4kA | mm | 768 x 307 x 1030h | 768 x 307 x 1030h | 768 x 307 x 1030h | 788 x 307 x 1083h |
| Weight – Up to 8kA | kg | 162 | 162 | 167 | |
| Dimensions – Up to 8kA | mm | 790 x 360 x 1030h | 790 x 360 x 1030h | 790 x 360 x 1030h | |
| Execution [F= Fixed; W= Withdrawable] | F/W | F/W | F/W | F/W |