LTNS
1000/1250

CARATTERISTICHE
MECCANICHE
|
TIPO
|
POLI
|
N° MAX.
BLOCCHI
TIPO
|
PESO
|
TEMPO MANOVRA
|
INGOMBRI MAX.
|
ATTACCO CAVI
|
|
CHIUSURA
|
APERTURA
|
| A |
B |
C |
D |
R |
S |
V |
M |
I |
| LTNS |
N° |
SK11 |
[KG] |
[ms] |
[ms] |
[mm] |
[mm] |
[mm] |
[mm] |
[mm] |
[mm] |
[mm] |
[mm] |
[mm] |
| 1000 |
1 |
4 |
22 |
240 |
30 |
125 |
350 |
50 |
459 |
69.5 |
362 |
11.5 |
266.5 |
- |
| 2 |
4 |
40 |
280 |
50 |
230 |
350 |
50 |
459 |
69.5 |
362 |
11.5 |
266.5 |
110 |
| 3 |
4 |
58 |
280 |
50 |
340 |
350 |
50 |
459 |
69.5 |
362 |
11.5 |
266.5 |
110 |
| 1250 |
1 |
4 |
24 |
240 |
30 |
125 |
350 |
50 |
459 |
69.5 |
362 |
11.5 |
266.5 |
- |
| 2 |
4 |
43 |
280 |
50 |
230 |
350 |
50 |
459 |
69.5 |
362 |
11.5 |
266.5 |
110 |
| 3 |
4 |
60 |
280 |
50 |
340 |
350 |
50 |
459 |
69.5 |
362 |
11.5 |
266.5 |
110 |
CARATTERISTICHE
ELETTRICHE
|
TIPO
LTNS
|
MAX V
[V]
|
ITH
[A]
|
POTERE
CHIUSURA
Ich
[A]
|
POTERE INTERRUZIONE C.C.
[A]
L/R
= 15ms
|
| 440V |
750V |
1000V |
| 1P |
2P |
1P |
2P |
1P |
2P |
| 1000 |
1000 |
1100 |
16000 |
4000 |
7000 |
2500 |
5000 |
1800 |
3500 |
| 1250 |
1000 |
1300 |
20000 |
5000 |
9000 |
3500 |
7000 |
2000 |
4000 |
|
TYPE
|
POTERE INTERRUZIONE C.A.[A]
COS
j
=
0.5
|
CORRENTE
MAX. IMPIEGO
PER
MOTORI C.A. E C.C.
|
| LTNS |
440V |
750V |
1000V |
A.C.
2-3 |
D.C.
2-3 |
D.C.
4.5 |
| 1000 |
10000 |
6000 |
5000 |
750 |
750 |
600 |
| 1250 |
12500 |
8000 |
6000 |
900 |
900 |
800 |
* With ceramic
arc chutes
DIMENSIONI
MONTAGGIO
|
TIPO
LTNS
|
POLI
|
a |
b |
c |
d |
e |
f |
g |
h |
PIASTRA DI FISSAGGIO
|
|
1000/1250
|
1 |
275 |
100 |
15 |
70 |
15 |
70 |
15 |
11 |
 |
| 2 |
275 |
210 |
15 |
180 |
15 |
180 |
15 |
11 |
| 3 |
275 |
320 |
15 |
190 |
15 |
290 |
15 |
11 |
DISTANZE DA PARTI ADIACENTI*
|
TIPO
|
METALLICCHE
A MASSA
|
ISOLATE
|
POSIZIONE DI MONTAGGIO**
|
| LTNS |
X |
Y |
X |
Y |
 |
| 1000 |
180 |
180 |
120 |
120 |
| 1250 |
200 |
200 |
120 |
120 |
*
Distanze per poteri d'interruzione nominale
**Per il montaggio orizzontale contattare il nostro ufficio
tecnico |
PRESTAZIONI CONTATTI AUSILIARI PER 10^6
MANOVRE
|
CORRENTE ALTERNATA REGIME
|
AC11 |
V- |
48 |
110 |
220 |
380 |
CONTATTI AUSILIARI
|
| I
[A] |
8 |
6 |
5 |
3 |
|
CORRENTE CONTINUA REGIME
|
DC11 |
V= |
24 |
48 |
110 |
250 |
SINISTRA
|
DESTRA
|
|

|

|
|
CARICO RESISTIVO
|
- |
I
[A] |
8 |
6 |
5 |
3 |
|
CARICO INDUTTIVO
|
15
ms |
I
[A] |
6 |
4 |
3 |
1.5 |
|
CARICO INDUTTIVO
|
300
ms |
I
[A] |
2.5 |
1.5 |
0.8 |
0.25 |
CONSUMO BOBINA PER CONTATTORI
LTN V/S
| TIPO |
1000/1250 |
| POLI |
1 |
2 |
3* |
| [W] |
60 |
80 |
150 |
DISTANZE MINIME
DI MONTAGGIO

Le
quote prevedono due blocchi di contatti ausiliari
HOME
|