LTNS 320/450


CARATTERISTICHE MECCANICHE

TIPO

POLI

N° MAX.
BLOCCHI

TIPO

PESO

TEMPO MANOVRA

INGOMBRI MAX

ATTACCO CAVI

CHIUSURA

APERTURA

A B C D R S V M I
LTNS SK11 [KG] [ms] [ms] [mm] [mm] [mm] [mm] [mm] [mm] [mm] [mm] [mm]
320 1 4 12 160 35 105 260 25 350 55 232 13 213 -
2 4 17 160 35 186 260 25 350 55 232 13 213 91
3 4 24 160 35 277 260 25 350 55 232 13 213 91
450 1 4 13 160 35 105 260 20 360 55 232 13 213 -
2 4 18 160 35 186 260 20 360 55 232 13 213 91
3 4 25 160 35 277 260 20 360 55 232 13 213 91

CARATTERISTICHE ELETTRICHE

TIPO

LTNS

MAX V

[V]

ITH

[A]

POTERE CHIUSURA

Ich [A]

POTERE INTERRUZIONE C.C. [A]

L/R = 15ms

440V 750V 1000V
1P 2P 1P 2P 1P 2P
320 1000 320 7000 800 1500 600 1200 400 800
450 1000 450 8000 1300 2500 1000 1800 600 1200

TIPO

POTERE INTERRUZIONE C.A. [A]
COS j = 0.5

CORRENTE MAX. IMPIEGO
PER MOTORI C.A. E C.C.

LTNS 440V 750V 1000V A.C. 2-3 D.C. 2-3 D.C. 4.5
320 2500 1800 1200 200 180 160
450 4000 2500 1800 280 250 200
*Con caminetti ceramici

DIMENSIONI DI FISSAGGIO

TIPO

LTNS

POLI

a b c d e f g h

PIASTRA FISSAGGIO

320/450

1 230 90 15 60 15 60 12,5 9
2 230 180 15 150 15 150 12,5 9
3 230 272 15 242 15 242 12,5 9

DISTANZE DA PARTI ADIACENTI*

TIPO

METALLICHE
A MASSA

ISOLATE

POSIZIONE DI MONTAGGIO**

LTNS X Y X Y
320 100 100 60 60
450 120 120 80 80
* Distanze per poteri di interruzione nominale
** Per il montaggio orizzontale interpellare sempre il nostro ufficio tecnico

PRESTAZIONI CONTATTI AUSILIARI PER 10^6 MANOVRE

CORRENTE ALTERNATA REGIME

AC11 V- 48 110 220 380

CONTATTI AUSILIARI

I [A] 8 6 5 3

CORRENTE CONTINUA REGIME

DC11 V= 24 48 110 250

SINISTRA

DESTRA

CARICO RESISTIVO

- I [A] 8 6 5 3

CARICO INDUTTIVO

15 ms I [A] 6 4 3 1.5

CARICO INDUTTIVO

300 ms I [A] 2.5 1.5 0.8 0.25

CONSUMO BOBINA PER CONTATTORI LTN V/S

TIPO 320/450
POLI 1 2 3*
[W] 40 40 90

DISTANZE MINIME DI MONTAGGIO

Le quote prevedono due blocchi di contatti ausiliari

HOME