| CONTACTORS
TYPE TADN
Characteristics of the field circuit
E = Rated
nominal voltage of excitation circuit;
Ec = Exciter ceiling voltage (Ec = 140%E)
If = Rated nominal current of excitation circuit
Kdc·If = Medium value of the field current under armature
circuit fault conditions, at the instant of the contactor's opening;
Kc·If = Peak value of the field current under armature circuit
fault conditions at the instant of the contactor's opening;
Iccf = Field current under field circuit fault conditions with voltage
= Ec;
Rd = Value of the disharge resistor in ohms.
Characteristics of the contactor
- Rated nominal
voltage Vn=E
- Rated continuous
current of main contacts In=1,1 If
- Rated short-time
voltage of main contacts V'=Ec
- Rated maximum
interrupting voltage of main contacts Vcc=Kdc·If·Rd+E
- Rated interrupting
current of main contacts at V' (short-circuit in the field circuit)
I'cc=Iccf
- Rated interrupting
current of main contacts at Vcc (short-circuit in the armature
circuit) Icc=Kdc·If+E/Rd
- Rated 1/2
second short-time current of the main contacts Icc0,5=Iccf
- Rated interrupting
current of the disharge contacts at V' Iccd=Ec/Rd
- Rated making
current of the disharge contacts (short-circuit in the armature
circuit) Ichd=Kc·If+Ec/Rd
- Rated 15
seconds short-time current of the discharge contacts Id15''