CONTACTORS TYPE TDN
CHANGE-OVER CONTACTORS TDN FROM 46 TO 4000 AMPS, 1000V A.C.&D.C.
A standard contactor
can be fitted with normally open poles (poles open when the contactors is deenergized) and
also with normally closed poles assembled on the same axle.
The extreme operational
conditions which can be obtained with a continuous adjustability, are the following:
a) when closing the
contactor, the N/C pole <<R>> opens before the closing of the normal pole
<<N>> and, viceversa, when opening, <<N>> opens before
<<R>> closes (type of adjustment suitable for the change-over contactors);
b) when closing the contactor, the pole <<R>> opens after closing of the pole
<<N>> and, viceversa when opening, <<R>> closes before
<<N>> opens (type of adjustment suitable for the field discharge contactors).
As already mantioned, the main
characteristic is the possibility of passing from one to the other of the two extreme
setting conditions with no-step, even adjusting within large limits the change-over time,
or the delay of one pole in respect of the other.
The poles type <<R>> are produced in standard sizes with rating up to 1000
Amps; for higher ratings poles of the existing sizes have to be connected in parallel.
It is also remarkable that the poles
<<R>>, besides with poles <<N>> of the same size, can be combined
with poles of different sizes as indicated in the table below. Of course the same
combinations can also be made with only poles <<R>> or only poles
<<N>> of different sizes.
The poles type <<R>> have the same overall dimensions of the poles
<<N>> but for the height.
Therefore the overall dimensions of the change-over contactors correspond exactly to those
of the normal contactors of the same size and number of poles, except for those indicated
in the table below.
Overall Dimensions of
N.C. pole (Table N°12)
| TYPE |
Figured Dimensions [mm] |
| C |
D |
I |
N |
O |
P |
Q |
R |
S |
T |
U |
| R 85 |
90 |
105 |
120 |
42 |
- |
- |
M6 |
- |
20 |
48 |
6,5 |
| R 125 |
90 |
115 |
130 |
42 |
- |
- |
M6 |
- |
20 |
48 |
8,5 |
| R 190 |
90 |
135 |
150 |
42 |
- |
- |
M8 |
- |
20 |
48 |
8,5 |
| R 270 |
140 |
170 |
195 |
50 |
- |
- |
M8 |
- |
25 |
57 |
8,5 |
| R 350 |
140 |
180 |
200 |
50 |
- |
- |
M8 |
- |
25 |
57 |
8,5 |
| R 550 |
140 |
195 |
230 |
52 |
- |
- |
M12 |
- |
40 |
70 |
13 |
| R 650 |
150 |
200 |
230 |
52 |
- |
- |
M12 |
- |
40 |
70 |
13 |
| R 800 |
80 |
295 |
350 |
173 |
110 |
18 |
M10 |
25 |
50 |
63 |
10,5 |
| R 1000 |
80 |
295 |
350 |
173 |
110 |
18 |
M10 |
25 |
50 |
63 |
10,5 |
| R 1250 |
80 |
295 |
350 |
173 |
110 |
18 |
M10 |
25 |
50 |
63 |
10,5 |

Electrical characteristics of the normally closed poles
(table N°13)
POLE TYPE
R |
Rated thermal current |
Breaking capacity A.C.
(R.M.S. value, cos =0,5)
[A] |
Breaking capacity D.C.
(Time constant L/R = 15 ms)
[A] |
Making
capacity |
Possible combination
with poles
N type |
| [A] |
220V |
380V |
550V |
110V |
220V |
440V |
600V |
[A] |
| R 85 |
85 |
1600 |
1300 |
1000 |
1600 |
1000 |
500 |
400 |
2500 |
85-125-190 |
| R 125 |
125 |
2000 |
1600 |
1250 |
2000 |
1250 |
700 |
500 |
3000 |
| R 190 |
190 |
2500 |
2000 |
1900 |
2500 |
1900 |
900 |
700 |
4000 |
| R 270 |
270 |
4500 |
3500 |
2700 |
4500 |
2700 |
1300 |
1000 |
6000 |
270-350-550-6503 |
| R 350 |
350 |
5000 |
4000 |
3500 |
5000 |
3500 |
1700 |
1200 |
7000 |
| R 550 |
550 |
6000 |
5000 |
4000 |
6000 |
4000 |
2000 |
1500 |
8000 |
| R 650 |
650 |
8000 |
6500 |
5000 |
8000 |
5000 |
2500 |
2000 |
10000 |
| R 800 |
800 |
10000 |
8000 |
7000 |
10000 |
7000 |
4000 |
3000 |
15000 |
800-3000 |
| R 1000 |
1000 |
12000 |
10000 |
8000 |
12000 |
8000 |
5000 |
3500 |
15000 |
| R 1250 |
1250 |
12000 |
10000 |
8000 |
12000 |
8000 |
5000 |
3500 |
20000 |
General Characteristics | Electrical Characteristics | Overall Dimensions | Contactors type TAN | Contactors type TADN | Contactors type NF, NFS, NHF | Contactors type CN