| BACK-UP PROTECTION
BY H.R.C. FUSES
For
applications in which fault currents larger than the contactor's
breaking capacity, or with peak values higher than those which cause
the repulsion of the contacts are experienced, protection is entrusted
to H.R.C. fuses that do not operate with currents within a limit
which the contactor can withstand but that, on the contrary, with
higher currents grant the full protection or a limited damage of
the contactor itself. The table below shows for the different types
of contactor the corresponding size of fuses recommended to obtain
respectively the full protection or a damage limited to the contacts'
welding.
(Table
n. 6)
| Contactor Type N |
|
85 |
125 |
190 |
270 |
350 |
550 |
650 |
800 |
1000 |
1250 |
| Max.Fuse |
c |
100 |
125 |
160 |
225 |
250 |
355 |
425 |
500 |
630 |
1000 |
Rating
[Amps.] |
b |
125 |
160 |
200 |
300 |
355 |
500 |
630 |
800 |
1000 |
1200 |