| OVERLOAD CAPABILITY
OF THE CONTACTORS
The contactors
can withsand for short time duration, current much higher than the
rated; in this instance two different phenomena must be considered:
the thermal and the electrodynamic. Dynamically the contactors can
withstand current peaks to a limit where repulsion of the contacts
may occur. The current which causes the repulsion of the contacts
could be higer than the making capacity of the contactor as it is
considered thet this phenomenon arises when the contactor is already
closed and operating. Therefore, the electrodynamic stress in this
case is not superimposed to the mechanical bounce effect that can
arise during the closing operation which is the principal cause
of the contacts melting. Of course, the intensity of this dynamic
current must also be thermally tolerable for the contactor and therefore,
in the table below, the values "Id" of the maximum accettable
dynamic currents are given providing that their duration is no more
than 100ms. From the thermal point of view the intensity of the
tolerable overload is inversely proportional to the duration and
depends essentially upon the time constant Tc of the warming-up
curve of the contactor when its rated current is applied. The diagram
below gives the ratio t/Tc (where t is the duration of the overload)
and the factor K which, when applied to the nominal current of the
contactor, determines the intensity of the tolerable overload starting
from the cold status.
(Table
n. 3)
| Contactor
Type N |
85 |
125 |
190 |
270 |
350 |
550 |
650 |
800 |
1000 |
1250 |
1600 |
2000 |
3000 |
| Id (Peak
val) [KA] |
3.5 |
4.5 |
5.5 |
9 |
11 |
13 |
15 |
20 |
29 |
40 |
40 |
40 |
55 |
Tc
[sec.] |
2150 |
1200 |
1500 |
2150 |
1300 |
2000 |
1500 |
1500 |
1400 |
1500 |
1800 |
2250 |
2150 |

HOME
|