| AUXILIARY
CONTACTS
Like
the main contacts, the auxiliary contacts can be easily varied to
meet most requirements. Four types of auxiliary contacts are available
:
- Type
P :instantaneous single contact, mounted on the
axies, with adjustable contact gap and pressure and with contact
elements in silver: N/O (normally open), N/C (normally closed) and
C/O (changeover) executions are available;
- Type
B : set of 10 instantaneous
contacts (5N/O + 5N/C), double interruption moulded type, mounted
together on a single frame and simultaneously controlled. Each set
type B takes the same space as two type P contacts.
All the contactors
of the sizes 270A and larger can be fitted with auxiliary poles
rating 46A or 60A with or without magnetic blow-outs and N/O or
N/C type.
Ratings
of the auxiliary contacts
(Table N°1)
| Contactor type |
Aux. Cont. Type |
Rated curr. [A] |
Breaking capacity
in AC Cosj=0,5 |
Breaking capacity
in DC L/R=30ms |
| 110V |
220V |
380V |
500V |
48V |
110V |
220V |
| N46-N60 |
P
B/L
|
5
-
|
5
-
|
3
-
|
3
-
|
-
-
|
2
-
|
1
-
|
0.5
-
|
| |
| N85 - N190 |
P
B/L
|
10
10
|
20
10
|
15
8
|
10
3
|
2
1.5
|
5
3
|
3
2
|
2
1
|
| |
| N270-N650 |
P
B/L
|
10
10
|
20
10
|
15
8
|
10
3
|
2
1.5
|
7
3
|
5
2
|
2
1
|
| |
| N800-N3000 |
P
B/L
|
15
10
|
20
10
|
20
8
|
15
3
|
5
1.5
|
8
3
|
5
2
|
2
1
|
HOME
|